A 24V DC DPDT relay from the Schneider Electric Zelio RUM series. This universal electromechanical plug-in relay is designed for high rated current use. Ideal for use in industrial machines, building machinery, medical equipment, packaging machines, textile machines, HVAC, etc.
Technical Specification
- Range of product: Zelio Relay
- Series name: Universal
- Product or component type: Plug-in relay
- Device short name: RUM
- Contacts type and composition: 2 C/O
- [Uc] control circuit voltage: 24 V DC
- [Ithe] conventional enclosed thermal current: 10 A at -40...55 °C
- Status LED: Without
- Control type: Lockable test button
- Utilisation coefficient 20 %
Complementary
- Shape of pin: Cylindrical
- [Ui] rated insulation voltage:
- 250 V conforming to IEC
- 300 V conforming to UL
- 300 V conforming to CSA
- [Uimp] rated impulse withstand voltage: 4 kV (1.2/50 µs)
- Contacts material: AgNi
- [Ie] rated operational current:
- 10 A at 28 V DC (NO) conforming to IEC
- 10 A at 250 V AC (NO) conforming to IEC
- 5 A at 28 V DC (NC) conforming to IEC
- 5 A at 250 V AC (NC) conforming to IEC
- 10 A at 30 V DC conforming to UL
- 10 A at 277 V AC conforming to UL
- 10 A at 277 V AC conforming to CSA
- 10 A at 30 V DC conforming to CSA
- Maximum switching voltage: 250 V conforming to IEC
- Resistive rated load:
- 10 A at 250 V AC
- 10 A at 28 V DC
- Maximum switching capacity: 2500 VA/280 W
- Minimum switching capacity: 170 mW at 10 mA, 17 V
- Operating rate:
- <= 18000 cycles/hour no-load
- <= 1200 cycles/hour under load
- Mechanical durability: 5000000 cycles
- Electrical durability 100000 cycles for resistive load
- Average coil consumption in W: 1.4 W
- Drop-out voltage threshold: >= 0.1 Uc DC
- Operate time: 20 ms at nominal voltage
- Release time: 20 ms at nominal voltage
- Average coil resistance: 470 Ohm at 20 °C +/- 15 %
- Rated operational voltage limits: 19.2...26.4 V DC
- Potection category: RT I
- Test levels Level: A group mounting
- Safety reliability data: B10d = 100000
- Operating position: Any position
- Product weight: 0.086 kg
- Device presentation: Complete product
- Dielectric strength:
- 2000 V AC between poles with basic insulation
- 1500 V AC between contacts with micro disconnection insulation
- 2500 V AC between coil and contact with reinforced insulation
- Standards:
- EN/IEC 61810-1
- UL 508
- CSA C22.2 No 14
- Vibration resistance:
- 3 gn (f = 10...150 Hz), amplitude +/- 1 mm (on 5 cycles in operation)
- 4 gn (f = 10...150 Hz), amplitude +/- 1 mm (on 5 cycles not operating)
- IP degree of protection: IP40
- Pollution degree: 3