LRD16 Schneider Relay Electric

  • Class 10A overload tripping
  • Screw terminals
  • Flame retardance conforms to UL 94

Product Description

A 9 to 13A differential thermal overload relay from the TeSys LRD series. The relay is controlled via Start and Stop push-buttons. Designed for motor protection applications.

Technical Specification 

  • Range: TeSys
  • Product or component type: Differential thermal overload relay
  • Device short name: LRD
  • Relay application: Motor protection
  • Product compatibility:
    • LC1D38
    • LC1D25
    • LC1D12
    • LC1D32
    • LC1D18
    • Network type:
      • DC
      • AC
    • Thermal protection adjustment range 9...13 A

    Complementary:

    •  Network frequency: 0...400 Hz
    • [Ue] rated operational voltage: 690 V AC 0...400 Hz
    • [Uimp] rated impulse withstand voltage: 6 kV
    • Phase failure sensitivity Tripping current 130 % of Ir on two phases, the last one at 0
    • Width: 45 mm
    • Depth: 70 mm
    • Product weight: 0.124 kg
    • Protective treatment TH conforming to IEC 60068
    • IP degree of protection IP20 conforming to IEC 60529
    • Ambient air temperature for operation -20...60 °C without derating conforming to IEC 60947-4-1
    • Ambient air temperature for storage -60...70 °C
    • Flame retardance V1 conforming to UL 94
    • Standards:
      • IEC 60947-5-1
      • EN 60947-4-1
      • ATEX D 94/9/CE
      • CSA C22.2 No 14
      • IEC 60947-4-1
      • EN 60947-5-1
      • UL 508