Schneider Electric Contactor 9A 24V 50/60HZ - LC1D09B7

Schneider ElectricSKU: LC1D09B7

Price:
£25.76

Description

LC1D09B7 Schneider Contc Electric

  • Control circuit voltage: 24V AC 50/60Hz
  • Rated breaking capacity: 250A at 440V for power circuit conforming to IEC 60947
  • Product certifications: BV, CCC, CSA, DNV, GL, GOST, RINA, UL

Product Description

From the TeSys LC1D series, a 3-pole (3 NO) category AC-1 / AC-3 contactor rated at 9A (AC-3) / 25A (AC-1) with a 24V AC coil.

Technical Specification 

  • Range: TeSys
  • Product name: TeSys D
  • Product or component type: Contactor
  • Device short name: LC1D
  • Contactor application:
    • Motor control
    • Resistive load
  • Utilisation category:
    • AC-3
    • AC-1
    • AC-4
  • Poles description: 3P
  • Power pole contact composition: 3 NO
  • [Ue] rated operational voltage:
    • <= 300 V DC for power circuit
    • <= 690 V AC 25...400 Hz for power circuit
  • [Ie] rated operational current:
    • 25 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
    • 9 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
    • Motor power KW:
      • 2.2 kW at 400 V AC 50/60 Hz AC-4
      • 2.2 kW at 220...230 V AC 50/60 Hz AC-3
      • 4 kW at 380...400 V AC 50/60 Hz AC-3
      • 5.5 kW at 500 V AC 50/60 Hz AC-3
      • 5.5 kW at 660...690 V AC 50/60 Hz AC-3
      • 4 kW at 415...440 V AC 50/60 Hz AC-3
    • Control circuit type: AC 50/60 Hz
    • [Uc] control circuit voltage: 24 V AC 50/60 Hz
    • Auxiliary contact composition: 1 NO + 1 NC
    • [Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947
    • [Ith] conventional free air thermal current:
      • 25 A at <= 60 °C for power circuit
      • 10 A at <= 60 °C for signalling circuit
    • Irms rated making capacity:
      • 250 A at 440 V for power circuit conforming to IEC 60947
      • 140 A AC for signalling circuit conforming to IEC 60947-5-1
      • 250 A DC for signalling circuit conforming to IEC 60947-5-1
    • Rated breaking capacity: 250 A at 440 V for power circuit conforming to IEC 60947
      • [Icw] rated short-time withstand current:
        • 105 A <= 40 °C 10 s power circuit
        • 210 A <= 40 °C 1 s power circuit
        • 30 A <= 40 °C 10 min power circuit
        • 61 A <= 40 °C 1 min power circuit
        • 100 A 1 s signalling circuit
        • 120 A 500 ms signalling circuit
        • 140 A 100 ms signalling circuit
      • Associated fuse rating:
        • 20 A gG at <= 690 V coordination type 2 for power circuit
        • 25 A gG at <= 690 V coordination type 1 for power circuit
        • 10 A gG for signalling circuit conforming to IEC 60947-5-1
      • Average impedance: 2.5 mOhm at 50 Hz - Ith 25 A for power circuit
      • [Ui] rated insulation voltage:
        • 600 V for power circuit certifications CSA
        • 600 V for power circuit certifications UL
        • 690 V for power circuit conforming to IEC 60947-4-1
        • 690 V for signalling circuit conforming to IEC 60947-1
        • 600 V for signalling circuit certifications CSA
        • 600 V for signalling circuit certifications UL

      Complementary:

      • Coil technology: Without built-in suppressor module
      • Control circuit voltage limits
        • 0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz
        • 0.8...1.1 Uc operational at 60 °C, AC 50 Hz
        • 0.85...1.1 Uc operational at 60 °C, AC 60 Hz
        • Inrush power in VA
          • 70 VA at 20 °C (cos ϕ 0.75) 60 Hz
          • 70 VA at 20 °C (cos ϕ 0.75) 50 Hz
          • Hold-in power consumption in VA
            • 7.5 VA at 20 °C (cos ϕ 0.3) 60 Hz
            • 7 VA at 20 °C (cos ϕ 0.3) 50 Hz
            • Heat dissipation: 2...3 W at 50/60 Hz
            • auxiliary contacts type
              • Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
              • Type mirror contact (1 NC) conforming to IEC 60947-4-1
              • Signalling circuit frequency: 25...400 Hz
                • minimum switching current: 5 mA for signalling circuit
                • minimum switching voltage: 17 V for signalling circuit
                • Non-overlap time
                  • 1.5 ms on energisation between NC and NO contact
                  • 1.5 ms on de-energisation between NC and NO contact
                  • Insulation resistance: > 10 MOhm for signalling circuit

                  Downloads

                  LC1D09B7 Instructions

                   

                   

                  LC1D09B7 Datasheet

                    Payment & Security

                    Amazon American Express Apple Pay Google Pay Maestro Mastercard PayPal Shop Pay Visa

                    Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

                    You may also like