Schneider Electric Contactor 18A 24V 50/60HZ - LC1D18B7

Liquid error (product-info line 70): -Infinity
Schneider ElectricSKU: LC1D18B7

Price:
£39.45

Description

LC1D18B7 Schneider Contc Electric

  • Control circuit voltage: 24V AC 50/60Hz
  • Rated breaking capacity: 250A at 440V for power circuit conforming to IEC 60947
  • Product certifications: BV, CCC, CSA, DNV, GL, GOST, RINA, UL

Product Description

From the TeSys LC1D series, a 3-pole (3 NO) category AC-1 / AC-3 contactor rated at 18A (AC-3) / 32A (AC-1) with a 24V AC coil.

Technical Specification 

  • Range: TeSys
  • Product or component type: Contactor
  • Device short name: LC1D
  • Contactor application:
    • Resistive load
    • Motor control
  • Utilisation category:
    • AC-4
    • AC-1
    • AC-3
  • Poles description: 3P
  • Power pole contact composition 3 NO
  • [Ue] rated operational voltage:
    • <= 300 V DC for power circuit
    • <= 690 V AC 25...400 Hz for power circuit
  • [Ie] rated operational current:
    • 18 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
    • 32 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
  • Motor power KW:
    • 10 kW at 500 V AC 50/60 Hz AC-3
    • 10 kW at 660...690 V AC 50/60 Hz AC-3
    • 4 kW at 220...230 V AC 50/60 Hz AC-3
    • 7.5 kW at 380...400 V AC 50/60 Hz AC-3
    • 9 kW at 415...440 V AC 50/60 Hz AC-3
    • 4 kW at 400 V AC 50/60 Hz AC-4
  • Control circuit type: AC 50/60 Hz
  • [Uc] control circuit voltage: 24 V AC 50/60 Hz
  • Auxiliary contact composition: 1 NO + 1 NC
  • [Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947
  • Overvoltage category: III
  • [Ith] conventional free air thermal current:
    • 32 A at <= 60 °C for power circuit
    • 10 A at <= 60 °C for signalling circuit
  • Standards:
    • CSA C22.2 No 14
    • EN 60947-4-1
    • EN 60947-5-1
    • IEC 60947-4-1
    • IEC 60947-5-1
    • UL 508

Complementary

    • Coil technology Without built-in suppressor module
    • Control circuit voltage limits
      • 0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz
      • 0.8...1.1 Uc operational at 60 °C, AC 50 Hz
      • 0.85...1.1 Uc operational at 60 °C, AC 60 Hz
    • Inrush power in VA
      • 70 VA at 20 °C (cos ϕ 0.75) 60 Hz
      • 70 VA at 20 °C (cos ϕ 0.75) 50 Hz
    • Hold-in power consumption in VA
      • 7.5 VA at 20 °C (cos ϕ 0.3) 60 Hz
      • 7 VA at 20 °C (cos ϕ 0.3) 50 Hz
    • Heat dissipation: 2...3 W at 50/60 Hz
    • Auxiliary contacts type
      • Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
      • Type mirror contact (1 NC) conforming to IEC 60947-4-1
    • Signalling circuit frequency: 25...400 Hz
      • minimum switching current: 5 mA for signalling circuit
      • minimum switching voltage: 17 V for signalling circuit
    • Non-overlap time
      • 1.5 ms on energisation between NC and NO contact
      • 1.5 ms on de-energisation between NC and NO contact
    • Insulation resistance: > 10 MOhm for signalling circuit

    Downloads

    LC1D18B7 Instructions

    LC1D18B7 Datasheet

    Payment & Security

    Amazon American Express Apple Pay Google Pay Maestro Mastercard PayPal Shop Pay Visa

    Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

    You may also like